central air not blowing

Steve -- Monday, 8 July 2002, at 12:12 a.m.

I have recently installed a new compressor unit (two yrs) and seems to be fine - compressor and fan are running, inside the house I can hear the heater unit fan but putting my hand to one of the vents I feel faint (cold enough) blowing and the house is heating up - no velocity in the central air to keep up with the heat.

Re: central air not blowing

Dan O. -- Monday, 8 July 2002, at 8:51 p.m.

: I have recently installed a new compressor unit

I assume you mean condenser unit (the whole part outside). The compressor is just one component inside of that.

: (two yrs) and seems to be fine - compressor
: and fan are running, inside the house I can
: hear the heater unit fan but putting my hand
: to one of the vents I feel faint (cold
: enough) blowing and the house is heating up
: - no velocity in the central air to keep up
: with the heat.

It could be that the evaporator (cooling) coil inside the furnace has frosted oven and is now hampering air flow through it or may be as simple as you furnace filter is plugged and needs changing. It could also be that the motor is not running at full speed and needs to be looked at.

Dan O.

Re: central air not blowing

steve -- Tuesday, 9 July 2002, at 9:46 a.m.

: I assume you mean condenser unit (the whole
: part outside). The compressor is just one
: component inside of that.

: It could be that the evaporator (cooling) coil
: inside the furnace has frosted oven and is
: now hampering air flow through it or may be
: as simple as you furnace filter is plugged
: and needs changing. It could also be that
: the motor is not running at full speed and
: needs to be looked at.

: Dan O.

OK, thanx, we got in there, someone else told me about ic(e)ing up, we found inside the coils caked w/ hair and (dirt)... cleaned it with a wire brush and it is fine now. Really appreciate this service.

sl

Re: central air not blowing

Dan O. -- Tuesday, 9 July 2002, at 1:35 p.m.

: OK, thanx, we got in there, someone else told
: me about ic(e)ing up, we found inside the
: coils caked w/ hair and (dirt)... cleaned it
: with a wire brush and it is fine now. Really
: appreciate this service.

Glad to hear it. Make sure you replace the furnace filter at the same time and several times a year to maintain efficiency and proper air flow.

Dan O.

Re: central air not blowing

steve -- Wednesday, 10 July 2002, at 10:43 a.m.

: Glad to hear it. Make sure you replace the
: furnace filter at the same time and several
: times a year to maintain efficiency and
: proper air flow.

: Dan O.

Got it! Thanx, No reply necessary.

sl


RepairClinic.com - Online appliance parts, FREE repair advice
Overnight or Rapid Shipping available to your home or office!


Return to the Appliance411 Home Page
Appliance411 Home

Repair Parts | Archive Search | Q&A Forum | Refer this Page

All forum content Copyright © Appliance411 & the respective author.
All rights reserved. 1997-2014
Please support Appliance411
Click to find out how